Central Wayne Energy Recovery, L.P. - Permitting Information
1. Facility Information
Central Wayne Energy Recovery, L.P.
2. Location
4901 Inkster, Dearborn Heights, MI
3. Distance from US/Canada Border
30 miles
4. Facility Type and Size
existing municipal waste incinerator facility, 157 MMBtu/hour
5. Sources of Emissions
small municipal waste combustors ( 250 t/day each), one large combustor (300 t/day) and their associated burners; storage silos.
6. Type of Fuel
Natural gas
7. Type and Quantity of Emissions
PM10 - 3.69 PPH
SO2 - 49 PPH
NOx - 65.8 PPH
CO - 12.2 PPH for the small waste combustors and 14.6 PPH for the large waste combustor
HCl - 17.4 PPH
VOC - 2.4 PPH
8. Emission Control Technology
- fabric filter for PM/PM-10 and trace metals;
- Selective Non-Catalytic Reduction system (SNCR) using urea injection to control NOx;
- activated carbon injection, to reduce mercury, mercury chloride, and dioxin/furans;
- spray dryer absorber to reduce HCl, SO2, and acid gas removal;
9. Date Permit Application Received
3/21/2002
10. Stack Height and Diameter
- stack testing procedures and the location of the stack are in concordance with 40 CFR Part 60 Appendix A
- the exhaust gas from the municipal waste combustor is discharged from a stack at an exit point equal or more than 225 ft above ground level, with a maximum diameter of 10 ft;
11. Permit Agency Contact
Randy Telesz
Michigan Department of Environmental Quality,
Air Quality Division,
Hollister Building,
106 West Allegan Street
PO Box 30260
Lansing, MI, 48909 - 7760
Tel. 517 373- 7089