This is not the current EPA website. To navigate to the current EPA website, please go to www.epa.gov. This website is historical material reflecting the EPA website as it existed on January 19, 2021. This website is no longer updated and links to external websites and some internal pages may not work. More information »

New Source Review (NSR) Permitting

Lordstown Energy Center - Permitting Information

1. Facility Information

Lordstown Energy Center

2. Location

Henn Parkway, Lordstown, Ohio

3. Distance from US/Canada Border

68 m

4. Facility Type and Size

a nominal 940 MW combined cycle gas turbine (CCGT) facility

5. Sources of Emissions

2 combustion turbine generators, 2 heat recovery steam generators with supplemental duct firing, 1 steam turbine generator, 1 emergency diesel generator, one auxiliary boiler, 1 emergency fire pump, 1 mechanical draft cooling tower, storage tanks

6. Type of Fuel

Pipeline Quality Natural Gas, Ultra-Low Sulfur Diesel

7. Type and Quantity of Emissions

Summary of Proposed BACT/BAT Emission Limits and Associated Control Technologies for the Combustion Turbines

Pollutant Emission
Rate
(lb/MMBtu)
Emission
Rate (ppmv)
at 15% O2
Control
Technology
Represents
NOx
CTG only
CTG w/ DB

0.0076
0.0077

2.0
2.0
DLN and
SCR
BACT/BAT
VOC
CTG only
CTG w/ DB

0.0014
0.0027

1.0
2.0
Good combustion
controls and
oxidation catalyst
BACT/BAT
CO
CTG only
CTG w/ DB

0.0047
0.0047

2.0
2.0
Good combustion
controls and
oxidation catalyst
BACT/BAT
PM10/PM2.5
CTG only
CTG w/ DB

0.0068
0.0049

n/a
n/a
Low sulfur fuel BACT/BAT
SO2
CTG only
CTG w/ DB

0.0015
0.0015

n/a
n/a
Low sulfur fuel BAT
H2SO4
CTG only
CTG w/ DB

0.0011
0.0011

n/a
n/a
Low sulfur fuel BACT/BAT
GHG 833 lb CO2e/MW-hr (at full load ISO conditions without duct firing) n/a High efficient
combustion
technology
BACT/BAT

Summary of Proposed BACT/BAT Emission Limits and Associated Control Technologies for the Auxiliary Boiler

Pollutant Emission Rate
(lb/MMBtu)
Control Technology Represents
NOx 0.02 Flue Gas Recirculation (FGR) and low NOx burner BACT/BAT
VOC 0.006 Good combustion controls BACT/BAT
CO 0.055 Good combustion controls BACT/BAT
PM10/PM2.5 0.008 Low sulfur fuel BACT/BAT
SO2 0.0015 Low sulfur fuel BAT
H2SO4 0.00011 Low sulfur fuel BACT/BAT
CO2e (GHG) 119 Good combustion controls
and Natural gas combustion
BACT/BAT

Summary of Proposed BACT/BAT Emission Limits and Associated Control Technologies for the Emergency Fire Pump

Pollutant Emission
Rate
(g/kW-hr)
Emission
Rate
(g/hp-hr)
Control
Technology
Represents
NOx 3.5 -- State-of-the-art
combustion design
BACT/BAT
VOC 0.5 -- State-of-the-art
combustion design
BACT/BAT
CO 5.0 -- State-of-the-art
combustion design
BACT/BAT
PM10/PM2.5 0.3 0.15 State-of-the-art
combustion design
BACT/BAT
SO2 -- 0.0048 Low sulfur fuel BAT
H2SO4 0.000132 -- Low sulfur fuel BACT/BAT
CO2e (GHG) 41 tpy   Efficient Design BACT/BAT

Summary of Proposed BACT/BAT Emission Limits and Associated Control Technologies for the Emergency Generator

Pollutant Emission
Rate
(g/kW-hr)
Emission
Rate
(g/hp-hr)
Control
Technology
Represents
NOx 5.2 3.88 State-of-the-art
combustion design
BACT/BAT
VOC 0.1 0.09 State-of-the-art
combustion design
BACT/BAT
CO 0.6 0.43 State-of-the-art
combustion design
BACT/BAT
PM10/PM2.5 0.2 0.15 State-of-the-art
combustion design
BACT/BAT
SO2 -- 0.0048 Low sulfur fuel BAT
H2SO4 0.000132 -- Low sulfur fuel BACT/BAT
CO2e (GHG) 683 tpy   Efficient Design BACT/BAT

8. Emission Control Technology

Dry low NOx burners, Catalytic Oxidation Systems #1 and #2, Selective Catalytic Reduction Systems #1 and #2 and High Efficiency Drift Eliminator

9. Date Permit Application Received

September 16, 2014

10. Stack Height and Diameter

  • Auxiliary Boiler:  160 ft, 2 ft
  • Emergency Generator:  14.9 ft, 1.52 ft
  • Emergency Fire Pump:  10 ft, 0.42 ft
  • Turbine #1:  160 ft, 22.5 ft
  • Turbine #2:  160 ft, 22.5 ft
  • Cooling Tower:  54 ft, 28 ft

11. Permit Agency Contact

Mike Hopkins
Ohio Environmental Protection Agency
Lazarus Government Center
122 S. Front Street
Columbus, OH 43215
(614) 644-3611