An official website of the United States government.

This is not the current EPA website. To navigate to the current EPA website, please go to www.epa.gov. This website is historical material reflecting the EPA website as it existed on January 19, 2021. This website is no longer updated and links to external websites and some internal pages may not work. More information »

LA 33.III.21 Subchap A, §2103. Storage of Volatile Organic Compounds; SIP effective August 4, 2011 (LAd34) and February 29, 2016 (LAd47) and September 28, (LAd58) to present.

Louisiana Administrative Code, Title 33 ENVIRONMENTAL QUALITY, Part III Air (LAC 33:III)
 
Chapter 21.  Control of Emission of Organic Compounds
 
Subchapter A.  General
 
Section 2103.  Storage of Volatile Organic Compounds, SIP effective August 4, 2011 (LAd34) and February 29, 2016 (LAd47) and September 28, (LAd58) to present.
 

Paragraphs in this compilation of Section 2103 SIP effective September 28, 2017 were approved by EPA:

LAc71E
Revisions to §2103 adopted in the Louisiana Register December 20, 1994 (20 LR 1376) (AQ92)
and submitted to EPA December 15, 1995 (LA-023).
This submittal was approved by EPA before the existence of Regulations.gov dockets.
Approved by EPA October 22, 1996 (61 FR 54737) effective December 23, 1996 (LAc71E) at
40 CFR 52.970(c)(71)(i)(E), now 52.999(c)(71)(i)(E) –- See Louisiana SIP History document. 
See Louisiana SIP History document for more information.
These revisions to §2103 are indicated in this compilation by:
AQ92 §2123,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)

LAd34
Revisions to §2103 approved by EPA July 5, 2011 (76 FR 38977) effective August 4, 2011 (LAd34)
Regulations.gov docket ID:  EPA-R06-OAR-2007-0924 [LA021]
This Federal Register approved multiple revisions to §2103 submitted to EPA between  1997 and 2006.
Errors in Federal Register amendatory language on page 76 FR 38982:
   (1) The State approval date for revisions to Section 2103.D.4.b.-2103.D.4.d should be
June 20, 1996, not August 20, 2002 -- The June 20, 1996, Louisiana Register is the only
Louisiana Register in submittals EPA acted on in this action that contains revisions to
paragraphs 2103.D.4.b. to 2103.D.4.d;
   (2) The State approval date for the revision to Section 2103.H.3 should be
January 20, 1998, not February 20, 1998.
Example approval line in this compilation of revisions to Section 2013 approved by EPA effective August 4, 2011 (LAd34):
Example: AQ137 §2103.G.1;LAd34;LA021.03;AQ137;LR22:0455(6/20/1996)

LAad47
Revision to paragraph 2103.D.4.a was adopted in the Louisiana Register October 20, 2007 (LR 33:2085) (MM002),
Submitted to EPA August 14, 2009 [LA039.03], and resubmitted to EPA October 2015,
Regulations.gov document EPA-R06-OAR-2012-0434-0005 [LA039.05].
Approved by EPA January 28, 2016 (81 FR 04891) effective February 29, 2016 (LAd47), Regulations.gov docket EPA-R06-OAR-2012-0434 [LA039].
MM002 §2103.D.4.a,LAd47;LA039.05;MM002;LR33:2085(10/20/2007).

LAd58 
Revision to paragraph §2103.G.5 and addition of new paragraphs §2103.G.6 and
§2103.G.7 adopted in the Louisiana Register October 20, 2010 (36 LR 2271)(AQ312)
and submitted to EPA August 29, 2013 (LA-129),
Regulations.gov document EPA-R06-2013-0167-0004 [LA040.04]
Approved by EPA August 29, 2017 (82 FR 40949) effective September 28, 2017 (LAd58),
Regulations.gov docket EPA-R06-OAR-2013-0167 [LA040].
These revisions to §2103.G this compilation is indicated by;
AQ312 §2103.G;LAd58;LA040.04;AQ312;LR36:2271(10/20/2010),submitted to EPA August 29, 2013
NOTE: According to the August 29, 2017 Federal Register amendatory language on page 82 FR 40952,
2103.E.3 is not included in the SIP.  There is no paragraph 2103.E.3 in this compilation of
SIP-approved Section 2103.

IMPORTANT NOTE: This compilation of Section 2103 SIP effective September 28, 2017 assumes that the
removal of entries for Section 2103 listed in the amendatory language on page 82 FR 40951 of the
August 29, 2017 Federal Register (82 FR 50951) is a CFR correction and NOT the removal of the
respective paragraphs in the SIP-approved Section 2103 SIP effective September 28, 2017 (LAd58).

 
Unless otherwise indicated, paragraphs are as approved by EPA October 22, 1996 (61 FR 54737)
effective December 23, 1996 (LAc71E) at 40 CFR 52.970(c)(71)(i)(E), now in 52.999(c)(71)(i)(E).
See Louisiana SIP History document for more information. 
 
AQ186   §2103.A;LAd34;LA021.06;AQ186;LR25:0852(5/20/1999)
   A. No person shall place, store, or hold in any stationary
tank, reservoir, or other container of more than 250 gallons
(950 liters) and up to 40,000 gallons (151,400 liters) nominal
capacity any volatile organic compound, having a maximum
true vapor pressure of 1.5 psia or greater at storage
conditions, unless such tank, reservoir, or other container is
designed and equipped with a submerged fill pipe or a vapor
loss control system, as defined in Subsection E of this
Section, or is a pressure tank capable of maintaining
working pressures sufficient at all times under normal
operating conditions to prevent vapor or gas loss to the
atmosphere.
 
AQ186   §2103.B;LAd34;LA021.06;AQ186;LR25:0852(5/20/1999)
   B. No person shall place, store, or hold in any stationary
tank, reservoir, or other container of more than 40,000
gallons (151,400 liters) nominal capacity any volatile
organic compound having a maximum true vapor pressure of
1.5 psia or greater at storage conditions unless such tank,
reservoir, or other container is a pressure tank capable of
maintaining working pressures sufficient at all times under
normal operating conditions to prevent vapor or gas loss to
the atmosphere or is designed and equipped with a
submerged fill pipe and one or more of the vapor loss
control devices described in Subsections C, D, and E of this
Section.
 
AQ137   §2103.C to 2103.C.3;LAd34;LA021.03;AQ137;LR22:0454(6/20/1996)
   C. Internal Floating Roof. An internal floating roof
consists of a pontoon type roof, double deck type roof, or
internal floating cover which will rest or float on the surface
of the liquid contents and is equipped with a closure seal to
close the space between the roof edge and tank wall. All tank
gauging and sampling devices shall be gas tight except when
gauging or sampling is taking place. If the organic
compounds have a vapor pressure of 11.0 psia or greater
under actual storage conditions, the requirements of
Subsection F of this Section shall supersede the requirements
of this Subsection. In the parishes of Ascension, Calcasieu,
East Baton Rouge, Iberville, Livingston, Pointe Coupee, and
West Baton Rouge, the following additional requirements
apply:
      1. The closure seal shall consist of either:
         a. a liquid mounted seal consisting of a foam- or
liquid-filled seal mounted in contact with the liquid between
the wall of the storage vessel and the floating roof
continuously around the circumference of the tank;
         b. a mechanical shoe seal (metallic-type shoe seal)
consisting of a metal sheet held vertically against the wall of
the storage vessel by springs or weighted levers and connected
by braces to the floating roof. A flexible coated fabric
(envelope) spans the annular space between the metal sheet
and the floating roof; or
         c. two seals mounted one above the other so that each
forms a continuous closure that completely covers the space
between the wall of the storage vessel and the edge of the
internal floating roof. The lower seal may be vapor-mounted,
but both must be continuous.
      2. Each opening in the internal floating roof (except rim
space vents and automatic bleeder vents) shall be provided
with a projection below the liquid surface. In addition, each
opening (except for leg sleeves, bleeder vents, rim space
vents, column wells, ladder wells, sample wells, and stub
drains) shall be provided with a cover equipped with a gasket.
Automatic bleeder vents and rim space vents shall be gasketed
and ladder wells shall be equipped with a sliding cover.
      3. If the internal floating roof does not meet the
specifications of this rule, then the specifications shall be met
at the earlier of either the next scheduled maintenance
turnaround (when deinventorying and degassing occurs) or
December 1, 2005. Any request for an extension beyond
December 1, 2005, shall be examined on a case-by-case basis
and must be approved by the administrative authority*.
 
AQ137   §2103.D; LAd34; LA021.03; AQ137; LR22:454 ( 6/20/1996)
   D. External Floating Roof. An external floating roof
consist of a pontoon type roof, double deck type roof, or
external floating cover which will rest or float on the surface
of the liquid contents and is equipped with a primary closure
seal to close the space between the roof edge and tank wall
and a continuous secondary seal (a rim mounted secondary)
extending from the floating roof to the tank wall. In the
parishes of Ascension, Calcasieu, East Baton Rouge, Iberville,
Livingston, Pointe Coupee, and West Baton Rouge, the
primary closure seal shall consist of a liquid mounted seal or
a mechanical shoe seal, as defined in Subsection C.1.a and b
of this Section. Installation of the primary and secondary
seals in these parishes shall be within the same time
requirements as stipulated in Subsection C.3 of this Section.
 
AQ92 §2123.D.1,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
       1. A secondary seal is not required if:
 
AQ137   §2103.D.1.a;LAd34;LA021.03;AQ137;LR22:0454(6/20/1996)
         a. the tank is a welded tank storing a VOC with a vapor
pressure at storage conditions less than 4.0 psia and is also
equipped with a liquid mounted seal, a mechanical shoe seal,
or a seal deemed equivalent by the administrative authority*.
 
           b. the storage vessels are external floating roof tanks having nominal storage capacities of 420,000 gallons (1,589,900 liters) or less used to store produced crude oil or condensate prior to lease custody transfer.
 
AQ137   §2103.D.1.c;LAd34;LA021.03;AQ137;LR22:0454(6/20/1996)
         c. a mechanical shoe seal is used in a welded tank
which also has a secondary seal from the top of the shoe seal
to the tank wall (i.e., a shoe-mounted secondary).
 
           d. an alternate seal or seals can be used in lieu of the primary and secondary seals required herein provided the resulting emission is not greater than that which would have resulted if the primary and secondary seals were installed.  The equivalency demonstration will be made to the satisfaction of the administrative authority*.
 
       2. The seal closure devices required in LAC 33:III.2103.D shall:
           a. have no visible holes, tears, or other openings in the seal(s) or seal(s) fabric.
           b. be intact and uniformly in place around the circumference of the floating roof and the tank wall.
           c. not have gap areas, of gaps exceeding 1/8 inch (0.32 cm) in width between the secondary seal and the tank wall, in excess of 1.0 in^2 per foot of tank diameter (6.5 cm^2 per 0.3m).
           d. not have gap areas, of gaps exceeding 1/8 in (0.32 cm) in width between the primary seal and the tank wall, in excess of 10.0 in^2 per foot of tank diameter (65 cm^2 per 0.3m).
           e.  the secondary seals shall be visually inspected at least semiannually.  The secondary seal gap measurements shall be made annually at any tank level provided the roof is off its legs.  The primary seal gap measurements shall be made every five years at any tank level provided the roof is off its legs.  Conditions not up to standards described in LAC 33:III.2103.D.2 shall be recorded along with date(s) that the standards are not met and the administrative authority shall be notified within seven days.  To avoid noncompliance with this Section, repairs necessary to be in compliance must be initiated within seven working days of recognition of defective conditions by ordering appropriate parts. Repairs shall be completed within three months of the ordering of the repair parts.  However, if it can be demonstrated that additional time for repair is needed, the administrative authority may extend this deadline.
 
AQ137   §2103.D.3;LAd34;LA021.03;AQ137;LR22:0454(6/20/1996)
      3. Requirements for Covering Openings. All openings in
the external floating roof, except for automatic bleeder vents,
rim space vent, and leg sleeves, are to provide a projection
below the liquid surface. Except for automatic bleeder vents,
rim space vents, roof drains, and leg sleeves, each opening in
the roof is to be equipped with a cover, seal, or lid that is to be
maintained in a closed position at all times (i.e., no visible
gap) except when the device is in actual use. Automatic
bleeder vents must be closed at all times except when the roof
is floated off or landed on the roof leg supports. Rim vents
must be set to open when the roof is being floated off the roof
leg supports or at the manufacturer's recommended setting.
Any emergency roof drain must be equipped with a slotted
membrane fabric cover or equivalent cover that covers at least
90 percent of the opening. In the parishes of Ascension,
Calcasieu, East Baton Rouge, Iberville, Livingston, Point
Coupee, and West Baton Rouge, all covers, seals, lids,
automatic bleeder vents, and rim space vents are to be
gasketed.
 
AQ137   §2103.D.4;LAd34;LA021.03;AQ137;LR22:0454(6/20/1996)
      4. Requirements for Guide Poles and Stilling Well
Systems. Emissions from guide pole systems must be
controlled for external floating roof storage tanks with a
capacity greater than 40,000 gallons (approximately 151 m3)
and which store a liquid having a total vapor pressure of 1.5
psia or greater. The requirements of this Paragraph shall only
apply in the parishes of Ascension, Calcasieu, East Baton
Rouge, Iberville, Livingston, Pointe Coupee, and West Baton
Rouge.
 
§2103.4.a SIP effective August 4, 2011 (LAd34) to February 28, 2016
OS065   §2103.D.4.a;LAd34;LA021.11;OS065;LR31:2439(10/20/2005)
         a. Controls for nonslotted guide poles and stilling
wells shall include pole wiper and gasketing between the
well and sliding cover. Controls for slotted guide poles shall
include a float with wiper, pole wiper, and gasketing
between the well and sliding cover. The description of the
method of control and supporting calculations based upon
the Addendum to American Petroleum Institute Publication
Number 2517, Evaporative Loss from External Floating Roof
Tanks, (dated May 1994) shall be submitted to the Office of
Environmental Assessment, Air Quality Assessment
Division, for approval prior to installation.
 
§2103.D.4.a SIP effective February 29, 2016 (LAd47) to present
MM002 §2103.D.4.a,LAd47;LA039.05;MM002;LR33:2085(10/20/2007).
         a. Controls for nonslotted guide poles and stilling
wells shall include pole wiper and gasketing between the
well and sliding cover. Controls for slotted guide poles shall
include a float with wiper, pole wiper, and gasketing
between the well and sliding cover. The description of the
method of control and supporting calculations based upon
the Addendum to American Petroleum Institute Publication
Number 2517, Evaporative Loss from External Floating Roof
Tanks, (dated May 1994) shall be submitted to the Office of
Environmental Assessment for approval prior to installation.
 
AQ137   §2103.D.4.b; LAd34; LA021.03; AQ137; LR22:0455(6/20/1996) ????? or 8/20/2002
         b. Alternate methods of controls are acceptable if
demonstrated to be equivalent to the controls in Subsection
D.4.a of this Section. The administrative authority* must
approve alternate methods of control.
 
AQ137   §2103.D.4.c; LAd34; LA021.03; AQ137; LR22:0455(6/20/1996) ????? or 8/20/2002
         c. Installation of controls required by Subsection D.4
of this Section shall be required by November 15, 1996.
Requests for extension of the November 15, 1996, compliance
date will be considered on a case-by-case basis for situations
which require the tank to be removed from service to install
the controls and must be approved by the administrative
authority*.
 
AQ137   §2103.D.4.d;LAd34;LA021.03;AQ137;LR22:0455(6/20/1996) ????? or 8/20/2002
         d. Control systems required by Subsection D.4 of this
Section shall be inspected semiannually for rips, tears, visible
gaps in the pole or float wiper, and/or missing sliding cover
gaskets. Any rips, tears, visible gaps in the pole or float
wiper, and/or missing sliding cover gaskets shall be repaired
in accordance with this Paragraph in order to avoid
noncompliance. Repairs must be initiated by ordering
appropriate parts within seven working days after a defect
listed in this Subparagraph is identified. Repairs shall be
completed within three months of the ordering of the repair
parts. However, if it can be demonstrated that additional time
for repair is needed, the administrative authority may extend
this deadline.
 
AQ92 §2123.E,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
   E. Vapor Loss Control System.  A vapor loss control system consists of a gathering system capable of collecting the volatile organic compound vapors and a vapor disposal system capable of processing such organic vapors overall control efficiency of the vapor loss control system shall be a minimum of 95 percent.  All tank gauging and sampling devices shall be gas-tight except when gauging or sampling is taking place.
 
AQ92 §2123.F,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
   F. No person shall place, store or hold in any stationary tank, reservoir or other container of more than 40,000 gallons (151,400 liters) nominal capacity any volatile organic compound having a true vapor pressure of 11 psia or greater at storage conditions unless such tank, reservoir or other container is a pressure tank capable of maintaining working pressures sufficient at all times under normal operating conditions to prevent vapor or gas loss to the atmosphere or is designed and equipped with a submerged fill pipe and vapor loss control system in accordance with LAC 33:III.2103.E.
 
AQ312 §2103.G;LAd58;LA040.04;AQ312;LR36:2271(10/20/2010),submitted to EPA August 29, 2013
   G. Exemptions. The provisions of this Section (e.g.,
LAC 33:III.2103) do not apply to:
 
AQ137   §2103.G.1;LAd34;LA021.03;AQ137;LR22:0455(6/20/1996)
      1. existing and new storage tanks, located in any parish
other than the parishes of Ascension, Calcasieu, East Baton
Rouge, Iberville, Livingston, Pointe Coupee, and West Baton
Rouge, used for crude oil or condensate and having a nominal
storage capacity of less than 420,000 gallons (1,589,900
liters) unless such new tanks are subject to New Source
Performance Standards;
 
AQ137   §2103.G.2;LAd34;LA021.03;AQ137;LR22:0455(6/20/1996)
      2. tanks 420,000 gallons (1,589,900 liters) or greater,
located in any parish other than the parishes of Ascension
Calcasieu, East Baton Rouge, Iberville, Livingston, Point
Coupee, and West Baton Rouge, used to store produced crude
oil or condensate prior to lease custody transfer unless such
tanks are subject to New Source Performance Standards.
 
AQ175   §2103.G.3;LAd34;LA021.05;AQ175;LR24:2242(12/20/1998)
      3. existing and new storage tanks in the parishes of
Ascension, Calcasieu, East Baton Rouge, Iberville,
Livingston, Pointe Coupee, and West Baton Rouge that are
used for crude oil or condensate prior to lease custody transfer
and that have a nominal storage capacity of less than 420,000
gallons (1,589,900 liters) unless such new tanks are subject to
New Source Performance Standards; and
 
AQ175   §2103.G.4;LAd34;LA021.05;AQ175;LR24:2242(12/20/1998)
      4. JP-4 fuels stored in horizontal underground tanks;
 
§2103.G.5 SIP effective August 4, 2011 (LAd34) to September 27, 2017
AQ175   §2103.G.5;LAd34;LA021.05;AQ175;LR24:2242(12/20/1998)
      5. with regard to the requirements of Paragraph C.1 of
this Section, any storage tank that is used for less than two
weeks in the calendar year, provided that the tank is empty
and liquid-free when not in use.
 
§2103.G.5 SIP effective September 28, 2017 (LAd58) to present
AQ312 §2103.G.5;LAd58;LA040.04;AQ312;LR36:2271(10/20/2010),submitted to EPA August 29, 2013
      5. with regard to the requirements of Paragraph C.1 of
this Section, any storage tank that is used for less than two
weeks in the calendar year, provided that the tank is empty
and liquid-free when not in use;
 
§2103.G.6 SIP effective September 28, 2017 (LAd58) to present
AQ312 §2103.G.6;LAd58;LA040.04;AQ312;LR36:2271(10/20/2010),submitted to EPA August 29, 2013
       6. with regard to the submerged fill pipe provisions of
Subsection A of this Section, tanks, drums, or other
containers storing pyrophoric catalyst at the Vistalon
Production Facility of ExxonMobil Chemical Company’s
Baton Rouge Chemical Plant; and
 
§2103.G.7 SIP effective September 28, 2017 (LAd58) to present
AQ312 §2103.G.7;LAd58;LA040.04;AQ312;LR36:2271(10/20/2010),submitted to EPA August 29, 2013
       7. with regard to the submerged fill pipe provisions of
Subsections A and B of this Section, tanks, drums, or other
containers used for the storage of corrosive materials,
including but not limited to spent sulfuric acid and
hazardous waste, at the Baton Rouge facility of Rhodia Inc.
 
   H. Compliance Tests
 
AQ92 §2123.H.1,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
       1. Floating Roofs.  The seal gap area shall be determined by measuring the length and width of the gaps around the entire circumference of the seal.  A 1/8 inch (0.32 cm) uniform diameter probe shall be used for measuring gaps.  Only gaps greater than or equal to 1/8 inch (0.32 cm) shall be used in computing the gap area. The area of the gaps shall be accumulated to determine compliance with LAC 33:III.2103.D.2.c and d.  Compliance with the other provisions specified in LAC 33:III.2103.D.2.a and b and D.4 may be determined by visual inspection.
 
AQ92 §2123.H.2,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
       2. Add-On Control Devices.  The following test methods shall be used, where appropriate to measure control device compliance:
 
AQ145   §2103.H.2.a to H.2.d;LAd34;LA021.02;AQ145;LR22:1212p6(12/20/1996)
         a. Test Methods 1-4 (40 CFR part 60, appendix A, as incorporated
by reference at LAC 33:III.3003) for determining flow rates, as necessary;
         b. Test Method 18 (40 CFR part 60, appendix A, as incorporated by
reference at LAC 33:III.3003) for measuring gaseous organic compound
emissions by gas chromatographic analysis;
         c. Test Method 21 (40 CFR part 60, appendix A, as incorporated by
reference at LAC 33:III:3003) for determination of volatile organic compound leaks;
         d. Test Method 25 (40 CFR part 60, appendix A, as incorporated by reference
at LAC III.3003) for determining total gaseous nonmethane organic emissions as carbon;
 
AQ92 §2123.H.2.e,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
         e. Additional performance test procedures, or equivalent test methods, approved by the administrative authority*.
 
AQ149   §2103.H.3. to H.3.e;LAd34;LA021.05;AQ149;LR24:0020(1/20/1998)
      3. Vapor Pressure. The maximum true vapor pressure is
determined based upon the highest expected calendar-month
average of the storage temperature. The true vapor pressure
shall be determined from one of the following methods:
         a. from available data on the Reid vapor pressure;
         b. by ASTM Test Method D323 for the measurement
of Reid vapor pressure, and adjusted for actual storage
temperature using the nomographs contained in API Bulletin 2517;
         c. from standard reference texts;
         d. determined by ASTM Test Method D2879; or
         e. by another method approved by the administrative
authority*.
 
AQ92 §2123.I to §2123.I.5,LAc71E,AQ092;LR20:1376(12/20/1994),submitted to EPA December 15, 1995 (LA-23)
   I.  Monitoring/Recordkeeping/Reporting.  The owner/operator of any storage facility shall maintain records to verify compliance with or exemption from LAC 33:III.2103.  The records shall be maintained for at least two years and will include, but not be limited to, the following:
       1.  the results of inspections required by LAC 33:III.2103.D.2.e. and D.4 shall be recorded.
       2.  for vapor loss control systems (LAC 33:III.2103.E) the following information shall be recorded:
           a.  daily measurements of the exhaust gas temperature immediately downstream of a direct-flame incinerator;
           b.  daily measurements of the inlet and outlet temperature of a chiller, or catalytic incinerator;
           c.  results of monitoring outlet VOC concentration of carbon adsorption bed to detect breakthrough.
       3.  the date and reason for any maintenance and repair of the applicable control devices and the estimated quantity and duration of volatile organic compound emissions during such activities.
       4.  the results of any testing conducted in accordance with the provisions specified in LAC 33:III.2103.H.
       5.  records of the type(s) of VOC stored and the average monthly true vapor pressure of the stored liquid for any storage vessel with an external floating roof that is exempt from the requirements for a secondary seal and is used to store VOCs with a true vapor pressure greater than 1.0 psia.
 
AQ175   §2103.I.6;LAd34;LA021.05;AQ175;LR24:2242(12/20/1998)
      6. records of the type(s) of VOC stored and the length
of time stored for any storage tank exempted under Subsection
G.5 of this Section. Verbal notification to the administrator is
required in advance, if possible, but no later than 24 hours
after the tank starts filling.
 
AQ219A   §2103.I.7 to I.7.b;LAd34;LA021.09;AQ219A;LR28:1763(8/20/2002)
      7. records of planned routine maintenance performed
on the vapor loss control system, including the duration of
each time the vapor loss control system does not meet the
specifications of Paragraph E.1 or 2 of this Section, as
applicable, due to the planned routine maintenance. Such
records shall include the information specified as follows:
         a. the first time of day and date: the: requirements of
Subsection E of this Section were not met, at the beginning
of the planned routine maintenance; and
         b. the first time of day and date the requirements of
Subsection E of this Section were met, at the conclusion of
 the planned routine maintenance.
 
****End Louisiana Section 2103 SIP effective August 4, 2011***LAd34***LA021***uxs****
****End Louisiana Section 2103 SIP effective February 29, 2016***LAd47***LA039***w2h***
**End Louisiana Section 2103 SIP effective September 28, 2017**LAd58**LA040**xxb**y38**